| 引用本文: | 管浩南,麻坚,陈勇,冯炳,牟文鼎,楼文娟.输电塔装配式钢桁架承台抗震性能试验[J].哈尔滨工业大学学报,2026,58(2):109.DOI:10.11918/202501018 |
| GUAN Haonan,MA Jian,CHEN Yong,FENG Bing,MOU Wending,LOU Wenjuan.Experimental study of seismic performance of assembled steel truss cap for transmission tower[J].Journal of Harbin Institute of Technology,2026,58(2):109.DOI:10.11918/202501018 |
|
| |
|
|
| 本文已被:浏览 1739次 下载 475次 |
 码上扫一扫! |
|
|
| 输电塔装配式钢桁架承台抗震性能试验 |
|
管浩南1,麻坚2,陈勇1,冯炳3,牟文鼎4,楼文娟1
|
|
(1.浙江大学 建筑工程学院,杭州 310058;2.金华电力设计院,浙江 金华 321016;3.绍兴大明电力设计院有限公司, 浙江 绍兴 312000;4.中国能源建设集团浙江省电力设计院有限公司,杭州 310012)
|
|
| 摘要: |
| 为研究装配式钢桁架承台的抗震性能,设计、加工了1个足尺装配式钢桁架承台,并对其进行低周往复荷载试验,分析其破坏机制、滞回曲线、骨架曲线、刚度退化、延性、能量耗散能力和应变等。基于试验结果,采用ANSYS软件建立试件的有限元模型并进行参数分析,得到在不同参数下模型骨架曲线的变化趋势,并提出破坏前骨架曲线的经验公式。结果表明:试件以主材中部屈曲变形为主要破坏模式,当主材中部发生局部集中破坏时,试件达到极限承载力;试件能够承受较大的水平力,水平极限荷载约为水平荷载设计值的12倍,延性系数约为15,试件具有一定的延性和变形能力;试件的抗震性能主要随承台高度、主材径厚比、下压力的减小而提高,其破坏前骨架曲线的经验公式与有限元数据吻合较好。 |
| 关键词: 装配式钢桁架承台 山区输电线路 低周往复荷载试验 有限元分析 抗震性能 |
| DOI:10.11918/202501018 |
| 分类号:TU391 |
| 文献标识码:A |
| 基金项目:国网浙江省电力有限公司科技项目(BD2021JH-SJYXM003) |
|
| Experimental study of seismic performance of assembled steel truss cap for transmission tower |
|
GUAN Haonan1,MA Jian2,CHEN Yong1,FENG Bing3,MOU Wending4,LOU Wenjuan1
|
|
(1.College of Civil Engineering and Architecture, Zhejiang University, Hangzhou 310058, China; 2.Jinhua Electric Power Design Institute, Jinhua 321016, Zhejiang, China; 3.Shaoxing Daming Electric Power Design Institute Co., Ltd., Shaoxing 312000, Zhejiang, China; 4.China Energy Engineering Group Zhejiang Electric Power Design Institute Co., Ltd., Hangzhou 310012, China)
|
| Abstract: |
| To study the seismic performance of assembled steel truss cap, a full-scale specimen was designed and manufactured. Subsequently, low cyclic loading tests were conducted to analyze its failure mechanisms, hysteretic and skeleton curves, stiffness degradation, ductility, energy dissipation capacity and strain, etc. Based on the experimental results, a finite element model of the specimen was established using ANSYS for parametric analysis. The variation trends on skeleton curves of the model under different parameters were obtained, and an empirical formula of skeleton curve before destruction was proposed. The test results indicate that the specimen is mainly damaged by local buckling deformation at the mid-section of main material. When localized damage occurs at this central region, the specimen reaches its ultimate bearing capacity. The specimen can bear significant horizontal forces, with the horizontal ultimate load approximately 12 times the design value. The ductility coefficient is about 15, indicating that the specimen has considerable ductility and deformation ability. The seismic performance of the specimen improves mainly with the decrease of the height of the cap, the ratio of diameter to thickness of the main material and the downforce. Furthermore, the empirical formula of the skeleton curve before destruction aligns well with the finite element data. |
| Key words: assembled steel truss cap mountainous transmission line low cyclic loading test finite element analysis seismic performance |
|
|
|
|