Thermo-hygrometric characteristics of variable-frequency heat pump dehumidification unit with condensater heat recovery for shipbuilding
CSTR:
Author:
Affiliation:

(1.School of Architecture and Design, Harbin Institute of Technology, Harbin 150006, China;2.Key Laboratory of Cold Region Urban and Rural Human Settlement Environment Science and Technology(Harbin Institute of Technology), Ministry of Industry and Information Technology, Harbin 150090, China; 3.Hanfu Qidong Environmental Technology Co., Ltd., Qidong 226236, Jiangsu,China)

Clc Number:

TU834.9

Fund Project:

undefined

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    The shipbuilding industry faces challenges with low dehumidification efficiency, high energy consumption, and imprecise air supply control under high-temperature and high-humidity conditions. To address these challenges, this study developed a condensater heat recovery variable-frequency heat pump dehumidification unit and systematically evaluated its performance. The unit applied a dual-condenser parallel structure and a full-variable frequency control strategy, enabling the regulation of multi-parameters. A testing platform based on enthalpy difference laboratory was established to simulate a typical shipbuilding environment, i.e., at 35 ℃ and 70% relative humidity. The effects of compressor speed, heat exchange distribution between the two condensers, condenser fan frequency, and air supply velocity on the dehumidification performance were comprehensively examined. The performance was quantitatively assessed by coefficient of performance (COP) and specific moisture extraction rate (SMER). The results showed that optimal performance with COP of 4.36 and SMER of 4.01 kg/kWh was achieved at a compressor speed of 3 500 r/min, a condenser fan frequency of 30 Hz, a condenser heat exchange ratio of 5.17∶1, and an air supply velocity of 2.7 m/s. The unit demonstrated precise control of temperature and humidity under various operational conditions and exhibited excellent energy efficiency. The findings will provide an effective and energy-saving technical solution for industrial applications requiring strict humidity control, such as shipbuilding, and offer both theoretical and experimental support for the design and optimization of industrial dehumidification systems.

    Reference
    Related
    Cited by
Get Citation
Related Videos

Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:March 04,2025
  • Revised:
  • Adopted:
  • Online: October 27,2026
  • Published:
Article QR Code