Abstract:The damage to porcelain column-type electrical equipment is a primary cause of power supply interruptions. The value of the dynamic amplification factor (DAF) for the support directly affects the seismic performance assessment of porcelain column-type electrical equipment. To determine the DAF for typical porcelain column-type electrical equipment, this paper proposes a distributed parameter model that considers the bending stiffness of flanges. This model provides the frequency equation and the equation of motion balance under generalized support excitation for the support-equipment system. The accuracy of the simplified analytical model is validated by comparing its results with vibration test data from three typical porcelain column-type electrical devices and computational results from multi-degree-of-freedom models. Using the simplified analytical model, the influences of parameters such as the height ratio, mass ratio, stiffness ratio, and flange bending stiffness ratio on the natural frequency of the support-equipment system and the DAF for the equipment are analyzed. The results indicate that the height and cross-sectional dimensions of the support have the most significant impact on the DAF for the equipment. Specifically, the DAF increases as the height of the support increases and the cross-sectional dimensions decrease. Current code recommendations for support dynamic amplification factors tend to be conservative (i.e., understated). Based on the requirements for support height and stiffness specified in the standards, it is recommended that the DAF for brackets supporting double porcelain columns and porcelain column-type electrical equipment with oil tanks located at the bottom be set to 2.5. For porcelain column-type electrical equipment with oil tanks located at the top, the suggested DAF is 1.5.