Effects of water mal-distribution on thermostatic-expansion-valve stability
CSTR:
Author:
Affiliation:

(School of Energy and Power Engineering, Xi’an Jiaotong University, Xi’an 710049, China)

Clc Number:

TB 657.9

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    To explore the hunting behavior of the thermostatic-expansion-valve (TEV), dynamic characteristics of the TEV (TEX2 externally balanced type) control-loop ranged from stability to vibration were studied under the selected 7 sets of water mal-distribution experimentally. Results showed that as F2 dropped from 36.9% to 27.0%, the TEV control-loop was stable and the overall evaporator capacity decreased by only 3.4%. As F2 dropped from 27.0% to 9.1%, evaporator overall outlet temperature changed from stability to vibration. Its vibration amplitude increased gradually with the phase transformation from vapor to mist, indicating that hunting behavior of TEV control-loop occurred, and the overall evaporator capacity decreased by 14.1%. The superheated refrigerant gas from Circuit 1 outlet only provided sensible heat and couldn't evaporate the liquid refrigerant out of Circuit 2 into superheated steam. Consequently, refrigerant in the evaporator overall outlet was of a smaller superheat than the necessary minimal stable signal (MSS) of the TEV, even at two-phase state, and would inevitably give rise to the hunting of the TEV -controlled system according to the MSS theory. These experimental results might provide references for the design of the heat exchanger of multi-circuit refrigerating system.

    Reference
    Related
    Cited by
Get Citation
Related Videos

Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:March 20,2016
  • Revised:
  • Adopted:
  • Online: July 11,2017
  • Published:
Article QR Code