支架特性对瓷柱型电气设备地震反应放大系数的影响
CSTR:
作者:
作者单位:

(1.中国地震局地震工程与工程振动重点实验室(中国地震局工程力学研究所),哈尔滨 150080; 2.地震灾害防治应急管理部重点实验室,哈尔滨 150080)

作者简介:

孙刚(1997—),男,博士研究生; 戴君武(1967—),男,研究员,博士生导师

通讯作者:

中图分类号:

TM64;TU311.3

基金项目:

国家自然科学基金(52008382);中国地震局工程力学研究所基本科研业务费(2024C2,3C04);国家自然科学基金(52378542)


Influence of support characteristics on the amplification coefficient of seismic response in porcelain column electrical equipment
Author:
Affiliation:

(1.Key Laboratory of Earthquake Engineering and Engineering Vibration, China Earthquake Administration (Institute of Engineering Mechanics, China Earthquake Administration), Harbin 150080, China; 2.Key Laboratory of Earthquake Disaster Mitigation, Ministry of Emergency Management, Harbin 150080, China)

Fund Project:

undefined

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    瓷柱型电气设备的损坏是电力供应中断的主要原因之一,支架对电气设备动力放大系数的取值直接影响瓷柱型电气设备抗震性能的评估。为了确定支架对典型瓷柱型电气设备的动力放大系数,提出一种考虑法兰抗弯刚度的分布参数模型,给出支架设备体系的频率方程,以及在广义支座激励作用下的运动平衡方程。通过与3种典型瓷柱型电气设备的振动试验结果对比,验证简化分析模型的准确性。利用简化分析模型分析支架高度比、质量比、刚度比以及法兰抗弯刚度比等参数对支架设备体系的自振频率和动力放大系数的影响。结果表明,支架的高度与截面尺寸对设备的动力放大系数影响最大,支架对设备的动力放大系数随着支架高度的增加和截面尺寸的降低而增大,现行规范对于支架动力放大系数建议取值偏低。根据规范对于支架的高度和刚度的要求,双瓷柱和油箱位于底部的瓷柱型电气设备的支架动力放大系数建议取值为2.5,对于油箱位于顶部的瓷柱型电气设备的支架动力放大系数建议取值为1.5。

    Abstract:

    The damage to porcelain column-type electrical equipment is a primary cause of power supply interruptions. The value of the dynamic amplification factor (DAF) for the support directly affects the seismic performance assessment of porcelain column-type electrical equipment. To determine the DAF for typical porcelain column-type electrical equipment, this paper proposes a distributed parameter model that considers the bending stiffness of flanges. This model provides the frequency equation and the equation of motion balance under generalized support excitation for the support-equipment system. The accuracy of the simplified analytical model is validated by comparing its results with vibration test data from three typical porcelain column-type electrical devices and computational results from multi-degree-of-freedom models. Using the simplified analytical model, the influences of parameters such as the height ratio, mass ratio, stiffness ratio, and flange bending stiffness ratio on the natural frequency of the support-equipment system and the DAF for the equipment are analyzed. The results indicate that the height and cross-sectional dimensions of the support have the most significant impact on the DAF for the equipment. Specifically, the DAF increases as the height of the support increases and the cross-sectional dimensions decrease. Current code recommendations for support dynamic amplification factors tend to be conservative (i.e., understated). Based on the requirements for support height and stiffness specified in the standards, it is recommended that the DAF for brackets supporting double porcelain columns and porcelain column-type electrical equipment with oil tanks located at the bottom be set to 2.5. For porcelain column-type electrical equipment with oil tanks located at the top, the suggested DAF is 1.5.

    参考文献
    相似文献
    引证文献
引用本文

孙刚,柏文,戴君武,赵霄扬.支架特性对瓷柱型电气设备地震反应放大系数的影响[J].哈尔滨工业大学学报,2026,58(10):48. DOI:10.11918/202502014

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2025-02-13
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2026-10-27
  • 出版日期:
文章二维码